Water Analysis Results


Water Test Results from the distribution system 2003

 Analytical MethodDetection Limit mg/lDate AnalyzedResults mg/l
SouthWest of 495NorthEast of 495CD
Lab Sample ID---------------------------03-98-103-98-2  
Turbidity (NTU)2130B0.203-04-03NDND  
TDS2540C1703-10-03180220  
Color (color units)EPA003-04-0300  
Odor (TON)EPA103-04-0312  
ph4500 HB0.0103-04-037.27.2  
Alkalinity- Total (CaC03)2320B1003-07-035230  
Hardness (CaC03)*200.70.603-05-036139  
Calcium (Ca)200.70.103-05-031811  
Magnesium (Mg)200.70.103-05-034.22.7  
Aluminum (Al)200.70.01003-05-030.032ND  
Potassium (K)200.70.203-05-032.12.2  
Iron (Fe)200.70.0103-05-030.020.04  
Manganese (Mn)200.70.00103-05-030.0080.006  
Sulfate (SO4)4500SO4D403-12-03129.5  
Chloride (Cl)4500CL B0.503-05-037088  
Silver (Ag)200.70.00303-05-03NDND  
Copper (Cu)200.70.0103-05-03NDND  
Zinc (Zn)200.70.00103-05-030.0040.004  

Notes:

ND=non detectable
mg/l=miligrams per liter
MMCL=Massachusetts maximum contaminant level
MMCL for Iron and Manganese are for taste & staining considerations only

* A water softener only should be considered if the hardness is greater than 125 mg/l